Alpha HW110LC Table Saw: My outlet has two vertical prongs (NEMA 5-15). What can I do?

Created by Sam V, Modified on Fri, 22 May at 4:50 PM by Gabriel Izzo

Alpha HW110LC Table Saw · Power & Electrical
My Outlet Has Two Vertical Prongs (NEMA 5-15) — What Can I Do?
Applicable Model
Alpha HW110LC (2HP)
Electrical Safety
+
Do not use an adapter or force a NEMA 5-20P plug into a NEMA 5-15 outlet. Using an undersized circuit creates a risk of overheating, tripped breakers, fire, or equipment damage.
+
Outlet and breaker upgrades must be performed by a licensed electrician in compliance with local electrical codes. Never replace a breaker or receptacle yourself unless you are qualified to do so.
+
Do not operate the HW110LC on a 15-amp circuit. The saw can draw up to 16 amps on startup and will overload the circuit, potentially causing unsafe operating conditions.
Why NEMA 5-15 Is Not Sufficient
A NEMA 5-15 outlet is rated for only 15 amps.
The HW110LC draws up to 16 amps on startup, which will overload a 15-amp circuit and may result in tripped breakers or improper operation.
What You Need
A NEMA 5-20R receptacle (rated for 110–125V / 20A).
A dedicated 20-amp single-pole circuit breaker at the panel serving that outlet.
The saw ships with a NEMA 5-20P plug installed — no plug change is required once the correct receptacle is in place.
i

For further questions about power requirements for your HW110LC, please contact our support team.